26 June 2013

MCB Selection Guide.

Followings are the MCB Selection criteria:

  • The first characteristic is the overload which is intended to prevent the accidental overloading of the cable in a no fault situation. The speed of the MCB tripping will vary with the degree of the overload. This is usually achieved by the use of a thermal device in the MCB.
  •  The second characteristic is the magnetic fault protection, which is intended to operate when the fault reaches a predetermined level and to trip the MCB within one tenth of a second.
  •  The level of this magnetic trip gives the MCB its type characteristic as follows:
TYPE
TRIPPING CURRENT
OPERATING TIME
Type B
3 To 5 times F.L current
0.04 To 13 Sec
Type C
5 To 10 times F.L current
0.04 To 5 Sec
Type D
10 To 20 times F.L current
0.04 To 3 Sec
    • The third characteristic is the short circuit protection, which is intended to protect against heavy faults maybe in thousands of amps caused by short circuit faults.

    • The capability of the MCB to operate under these conditions gives its short circuit rating in Kilo amps (KA).
    In general for consumer units a 6KA fault level is adequate whereas for industrial boards 10KA fault capabilities or above may be required.

    Type B MCB is used for normal domestic loads like Light, Fan, Heating etc.

    Type C MCB is used for small inductive loads.

    Tpye D MCB is used for motor loads. 


    For more read: MCB and Wire selection chart