Transformer:
Secondary Amperes 1-phase=VA/Volts
Secondary
Amperes 3-phase=VA/Volts x 3
Secondary
Available fault 1-phase=VA/(Volts x %impedance)
Secondary
Available fault 3-phase=VA/(Volts x 3 x %impedance)
Delta:
Line Voltage=Phase Voltage
Delta:
Line Amperes=Phase Amps x Sqrt(3)
Wye
: Line Voltage=Phase Voltage x Sqrt(3)
Wye:
Line Amperes=Phase Amps
Base
Current = Base KVA / Base Voltage
Base
Impedance = Base Voltage / Base Current
Base
Impedance=Base Voltage KV2/Base MVA
Per
Unity Quantity = Actual Quantity / Base Quantity
Per
Unit Impedance = Impedance in ohms x MVA(Base) / KV(base)2
Znew(pu)=Zold(pu)
x (MVAnew/MVAold) x (KVold/KVnew)2
BUSBAR:
BUSBAR:
Fault
withstand capacity of Busbar = 35 KA RMS for one second
OTHERS:
Area of Circle=π r2
Length of Coiled Wire=Diameter of coil x Number of coil x π
Temperature oC = (Temp F - 32) / 1.8
Temperature oF = (temp C x 1.8) + 32